Note
Analog output status messages may not appear on the integral display while the
Rosemount 5300 Level Transmitter runs in HART 7 multidrop mode.
Table 7-7: Analog Output Status
Message Description Action
Not connected Analog output hardware is not
connected.
Alarm Mode The analog output is in Alarm Mode. Check Error and Warning Messages to
find the reason for the Alarm.
Saturated The analog output signal value is
saturated, i.e. equal to the saturation
value.
No action needed.
Multidrop The transmitter is in Multidrop Mode. The
analog output is fixed at 4 mA.
This is the normal setting when a device is
used in Multidrop configuration.
Fixed Current mode The analog output is in fixed current
mode.
This mode is used when calibrating the
Analog Output channel.
PV out of Limits The Primary variable is out of range. Check the Upper and Lower Range Value
Span Too Small The configured span is too small. Check the Upper and Lower Range Value.
Invalid Limits The given Upper and Lower Sensor Limits
are invalid.
Check that the difference between the
Upper and Lower Sensor Limits is greater
than the Minimum Span.
7.3 LCD error messages
Figure 7-1: The Rosemount 5300 Display Panel Displaying an Error Message
3
Table 7-8: Error Messages Displayed on the Rosemount 5300 Display Panel
Error message Description
RAM FAIL An error in the gauge data memory (RAM) has been
detected during the startup tests.
Note
This resets the gauge automatically.
Reference Manual Service and troubleshooting
00809-0100-4530 April 2019
Reference Manual 177