F.4 Diagnostics device errors
In addition to the BLOCK_ERR and XD_ERROR parameters, more detailed information on
the measurement status can be obtained via DIAGN_DEV_ALERT. Table F-17 lists the
potential errors and the possible corrective actions for the given values. The corrective
actions are in order of increasing system level compromises. The first step should always
be to reset the gauge and then if the error persists, try the steps in Table F-17. Start with
the first corrective action and then try the second.
Table F-17: Device Errors Diagnostics
Bit Number Value of DIAGN_DEV_ALERT Description Corrective action
0 No alarm active
0 0x00000001 Reserved
1 0x00000002 FF card to gauge comm fault Replace gauge
2 0x00000004 Level measurement failure Verify device installation and
configuration
3 0x00000008 Temperature measurement
failure
Check ambient temperature. If
ambient temperature ok
replace the device.
4 0x00000010 Volume measurement failure Check volume configuration
5 0x00000020 Database Error Load default database to the
device and reconfigure the
device
6 0x00000040 HW Error Replace device
7 0x00000080 Microwave Unit Error Replace device
8 0x00000100 Configuration Error Load default database to the
device and reconfigure the
device
9 0x00000200 SW Error Replace device
10 0x00000400 Invalid Strap Table Check the Strapping Table
configuration
11 0x00000800 Internal Temp Warning Check ambient temperature at
installation site
12 0x00001000 Database Warning Check the device configuration
13 0x00002000 HW Warning Check device installation and
configuration
14 0x00004000 Microwave Unit Warning Check device installation and
configuration
15 0x00008000 Configuration Warning Check the device configuration
16 0x00010000 SW Warning Check device installation and
configuration