5.6.2 Connect to device using a handheld communicator
Procedure
Turn on the handheld communicator and connect to the device.
5.6.3 Configure device
HART
®
Procedure
1. Select Configure Guided Setup.
2. Select Level Measurement Setup and follow the instructions.
3. Select Device Specific Setup.
4. Run Verify Level to check your level measurement.
5. Consider optional setup, such as Volume and Display.
FOUNDATION
Fieldbus
Procedure
1. Select Configure Guided Setup.
2. Select Level Measurement Setup and follow the instructions.
3. (Optional) Select Volume Calculation Setup.
4. (Optional) Select Device Specific Setup.
5. (Recommended) Select Restart Measurement. (Recommended)
5.7 Basic configuration using DeltaV
The Rosemount 5300 Level Transmitter supports DD Methods for DeltaV
to facilitate
transmitter configuration. The following description shows how to use DeltaV with AMS
Device Manager to configure the Rosemount 5300 Level Transmitter. The corresponding
FOUNDATION
Fieldbus commands are also shown.
Procedure
1. From the Start menu, select DeltaV Engineering DeltaV Explorer.
2. Navigate through the file structure to find the Rosemount 5300 Level Transmitter.
3. Right-click the Rosemount 5300 Level Transmitter icon and select Properties.
Configuration Reference Manual
April 2019 00809-0100-4530
140 Rosemount 5300 Level Transmitter