will also need the National Instruments Communication Manager software (see Installing
the RRM software for FOUNDATION Fieldbus).
5.3 Host system integration
5.3.1 Confirm system readiness (HART
®
only)
Confirm HART
®
revision capability
If using HART based control or asset management systems, confirm the HART capability of
those systems prior to transmitter installation. Not all systems are capable of
communicating with HART Revision 7 protocol.
Transmitters with a firmware version 2F0 or later can be configured for either HART
Revision 5 or 7.
Confirm correct device driver
Procedure
Verify that the latest Device Driver (DD/DTM
) is loaded on your systems to ensure
proper communication. See Table 5-1.
Download the latest Device Driver from Emerson.com/DeviceInstallKits.
Table 5-1: Rosemount 5300 Device Revisions and Files
Firmware version
(1)
Find Device Driver
HART
®
Universal Revision Device Revision
(2)
2F0 or later 7 4
5 3
2A2 - 2E0 5 3
(1) Firmware version is printed on the transmitter head label, e.g. SW 2E0 or can be found in
Rosemount Radar Master (select Device Properties).
(2) Device revision is printed on the transmitter head label, e.g. HART Dev Rev 4.
Switch HART
®
revision mode
If the HART configuration tool is not capable of communicating with HART Revision 7, the
device will load a generic menu with limited capability. To switch the HART revision mode
from the generic menu:
Procedure
1. Locate the “Message” field.
2. In the Message field, enter HART5 or HART7 and then 27 trailing spaces.