Figure 7-3: Flash Sequence Example
A. Seconds
7.5 FOUNDATION
™
Fieldbus error messages
7.5.1 Resource block
This section describes error conditions found in the Resource block. Read Table 7-10
through Table 7-12 to determine the appropriate corrective action.
Block errors
Table 7-10 lists conditions reported in the BLOCK_ERR parameter.
Table 7-10: Resource Block Block_Err Messages
Condition name and description
Other
Simulate Active: This indicates that the simulation switch is in place. This is not an indication that
the I/O blocks are using simulated data
Device Fault State Set
Device Needs Maintenance Soon
Memory Failure: A memory failure has occurred in FLASH, RAM, or EEPROM memory
Lost Static Data: Static data that is stored in non-volatile memory has been lost
Lost NV Data: Non-volatile data that is stored in non-volatile memory has been lost
Device Needs Maintenance Now
Out of Service: The actual mode is out of service
Table 7-11: Resource Block Summary_Status Messages
Condition name
Uninitialized
No repair needed
Repairable
Call Service Center
Service and troubleshooting Reference Manual