5. Secure the split pins.
3.5 Mount device on tank
Mount the transmitter with flange on a nozzle on top of the tank. The transmitter can also
be mounted on a threaded or Tri-Clamp
®
connection.
3.5.1
Tank connection with flange
Prerequisites
Note
PTFE covered probes must be handled carefully to prevent damage to the coating.
Procedure
1. Place a suitable gasket on top of the tank flange.
Note
Gasket should not be used for PTFE covered probe with protective plate.
Reference Manual Mechanical installation
00809-0100-4530 April 2019
Reference Manual 67