20. Tighten the outer pipe.
PP
7RUTXHIWOE1P
21. Tighten the two set screws.
PP
7RUTXHIWOE1P
22. Verify a gap of about 1 mm above the outer pipe.
Postrequisites
After shortening the probe make sure to update the transmitter configuration to the new
probe length.
3.4 Centering disc for pipe installations
To prevent the probe from contacting the chamber or pipe wall, centering discs are
available for flexible single, rigid single, and flexible twin lead probes. The disc is attached
to the end of the probe. Discs are made of stainless steel, Alloy C-276, Duplex 2205, or
PTFE. The centering disc in PTFE is not available for HTHP probes.
Mechanical installation Reference Manual
April 2019 00809-0100-4530
60 Rosemount 5300 Level Transmitter