Table F-1: Channel Assignments (continued)
Channel Name Channel Number Process variable
Signal Strength 4 CHANNEL_RADAR_SIGNAL_ST
RENGTH
Volume 5 CHANNEL_RADAR_VOLUME
Internal Temperature 6 CHANNEL_RADAR_INTERNAL_
TEMPERATURE
Upper Product Volume 7 CHANNEL_UPPER_PRODUCT_V
OLUME
Lower Product Volume 8 CHANNEL_LOWER_
PRODUCT_VOLUME
Interface Distance 9 CHANNEL_INTERFACE_
DISTANCE
Upper Product Thickness 10 CHANNEL_UPPER_
PRODUCT_THICKNESS
Interface Level 11 CHANNEL_INTERFACE_LEVEL
Interface Level Rate 12 CHANNEL_INTERFACE_
LEVELRATE
Interface Signal Strength 13 CHANNEL_INTERFACE_
SIGNALSTRENGTH
Signal Quality 14 CHANNEL_SIGNAL_QUALITY
Surface/Noise Margin 15 CHANNEL_
SURFACE_NOISE_MARGIN
Vapor DC 16 CHANNEL_VAPOR_DC
F.2 Parameters and descriptions
Table F-2: Level Transducer Block Parameters and Descriptions
Parameter Index Number Description
ST_REV 1 The revision level of the static data associated with the
function block. The revision value increments each
time a static parameter value in the block is changed.
TAG_DESC 2 The user description of the intended application of the
block.
STRATEGY 3 The strategy field can be used to identify grouping of
blocks. This data is not checked or processed by the
block.
ALERT_KEY 4 The identification number of the plant unit. This
information may be used in the host for sorting alarms,
etc.