Table K-4: Output Variables for Floating Point Format Code 2
Register Name Register Number Note
Slave 1 Status 2100 Bit information in bitfield:
Bit 0: Invalid Measurement
Slave 1 PV.
Bit 1: Invalid Measurement
Slave 1 SV.
Bit 2: Invalid Measurement
Slave 1 TV.
Bit 3: Invalid Measurement
Slave 1 FV.
Bit 14: HART bus busy (slave in
burst or other master present)
Bit 15: HTM Task not running
(option not available).
Note
Bit 1-3 is set when Invalid
Measurement of Slave 1 Non
PV, i.e. all three bits are set
simultaneously.
Slave 1 PV
2102 Primary variable from slave 1
represented in IEEE 754 format,
using Floating Point Format
Code 2.
Slave 1 SV 2104 Secondary variable from slave 1
represented in IEEE 754 format,
using Floating Point Format
Code 2.
Slave 1 TV 2106 Tertiary variable from slave 1
represented in IEEE 754 format,
using Floating Point Format
Code 2.
Slave 1 FV (QV) 2108 Fourth variable from slave 1
represented in IEEE 754 format,
using Floating Point Format
Code 2.
Reference Manual Rosemount 5300 with HART
®
to Modbus
®
Converter
00809-0100-4530 April 2019
Reference Manual 479