2. Follow the on-screen instructions.
Note
The offset (Calibration Distance parameter) is automatically set after completing
the Verify Level method. An offset greater than 4 in. (100 mm) indicates a problem
with the level measurement. Re-check configuration parameters. If these are
correct, then view an echo plot and evaluate thresholds.
Archive device
When configuration is finished, it is recommended that the configuration is saved to a
backup file.
The backup file may be useful to:
Install another Rosemount 5300 Level Transmitter in a similar tank since the file can be
directly uploaded to a new device.
Restore the configuration, if for any reason, configuration data is lost or accidentally
modified making the device inoperable.
Procedure
In the Guided Setup window, select Archive Device.