Table 7-18: Troubleshooting the HART to Modbus converter (continued)
Symptom Recommended actions
No communication with Levelmaster
protocol
See "No communication on RS-485 bus".
Make sure the “Modbus communication protocol configuration” is
done properly, see Modbus communication protocol configuration.
Make sure the Levelmaster address is unique on the bus.
Cycle the power, waiting 40 seconds before communication begins.
Check the RTU communication settings.
Service and troubleshooting Reference Manual
April 2019 00809-0100-4530
188 Rosemount 5300 Level Transmitter