Figure 7-6: Distance Calibration
$
%
A. Upper Reference Point
B. Distance
7.8.2
Calibrate level
Procedure
1. Measure the actual product level.
2. Adjust the Tank Height so the product level measured by the transmitter
corresponds to the actual product level.
Figure 7-7: Distance and Level Calibration
$
&
%
A. Upper Reference Point
B. Tank Height
C. Level
Reference Manual Service and troubleshooting
00809-0100-4530 April 2019
Reference Manual 193