D.6.2 Review installation guidelines
The following installation guidelines should be considered when mounting the
transmitter:
Only probe type 3V or 4U must be used. Check the “VC” and “R3” marking on the seal.
Figure D-7: “VC” and “R3” Marking
$%
A. Probe type 3V (coaxial) for 3-4 in. chambers
B. Probe type 4U (rigid single) for 2 in. chambers
The maximum probe length is 13 ft. 1 in. (4 m) for probe type 3V and 9 ft. 10 in. (3 m)
for probe type 4U.
Pipe/Chamber is the only supported mounting type. See below for supported pipe
inner diameters:
Probe type
Chamber size Supported pipe inner
diameter
3V 3 to 4 in. Minimum 2 in. (50 mm)
4U 2 in. 1.5 to 2.05 in. (38 to 52 mm)
Probe End Projection is disabled when Vapor Compensation is enabled.
Trim Near Zone shall not be used when Dynamic Vapor Compensation is used.
Dynamic Vapor Compensation requires a minimum distance X from the flange to the
surface level to measure the change in the vapor dielectric constant. If the level rises
within this area, the unit switches over to static compensation, using the last known
vapor dielectric constant.
Reference Manual Advanced configuration
00809-0100-4530 April 2019
Reference Manual 407