Table I-1: Resource Transducer Block Parameters (continued)
Parameter Index number Description
FAILED_ENABLE 70 Enabled FAILED_ALM alarm conditions. Corresponds bit for bit to the
FAILED_ACTIVE. A bit on means that the corresponding alarm
condition is enabled and will be detected. A bit off means the
corresponding alarm condition is disabled and will not be detected.
FAILED_MASK 71 Mask of FAILED_ALM. Corresponds bit of bit to FAILED_ACTIVE. A bit
on means that the condition is masked out from alarming.
FAILED_PRI 69 Designates the alarming priority of the FAILED_ALM.
FB_OPTION 45 Indicates which function block licensing options are enabled.
FEATURES 17 Used to show supported resource block options. The supported
features are: SOFT_WRITE_LOCK_SUPPORT,
HARD_WRITE_LOCK_SUPPORT, REPORTS, and UNICODE
FEATURES_SEL 18 Used to select resource block options.
FINAL_ASSY_NUM 54 The same final assembly number placed on the neck label.
FREE_SPACE 24 Percent of memory available for further configuration. Zero in a
preconfigured device.
FREE_TIME 25 Percent of the block processing time that is free to process additional
blocks.
GRANT_DENY 14 Options for controlling access of host computers and local control
panels to operating, tuning, and alarm parameters of the block. Not
used by device.
HARD_TYPES 15 The types of hardware available as channel numbers.
HARDWARE_REV 52 Hardware revision of the hardware that has the resource block in it.
HEALTH_INDEX 84 Parameter representing the overall health of the device, 100 being
perfect and 1 being non-functioning. The value is based on the active
PWA alarms.
ITK_VER 41 Major revision number of the inter operability test case used in
certifying this device as interoperable. The format and range are
controlled by the Fieldbus Foundation.
LIM_NOTIFY 32 Maximum number of unconfirmed alert notify messages allowed.
MAINT_ACTIVE 77 Enumerated list of maintenance conditions within a device.
MAINT_ALM 78 Alarm indicating the device needs maintenance soon. If the condition
is ignored, the device will eventually fail.
MAINT_ENABLE 75 Enabled MAINT_ALM alarm conditions. Corresponds bit for bit to the
MAINT_ACTIVE. A bit on means that the corresponding alarm
condition is enabled and will be detected. A bit off means the
corresponding alarm condition is disabled and will not be detected.
MAINT_MASK 76 Mask of MAINT_ALM. Corresponds bit of bit to MAINT_ACTIVE. A bit
on means that the condition is masked out from alarming.
MAINT_PRI 74 Designates the alarming priority of the MAINT_ALM
MANUFAC_ID 10 Manufacturer identification number – used by an interface device to
locate the DD file for the resource.
Reference Manual Resource Transducer Block
00809-0100-4530 April 2019