EasyManua.ls Logo

Emerson Rosemount 5400 Series - Page 101

Emerson Rosemount 5400 Series
314 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
89
Reference Manual
00809-0100-4026, Rev HA
Section 5: Basic Configuration/Start-up
November 2014
Basic Configuration/Start-up
Getting started
1. Before starting RRM make sure that appropriate settings are made with the National
Instruments Interface Configuration Utility:
Use the following settings:
Device address = Visitor
Device Type = Link Master Device
Usage = NI-FBUS
2. Start RRM: from the Start menu click Programs > Rosemount > Rosemount
RadarMaster or click the RRM icon in the Microsoft Windows workspace.
3. If the National Instruments Communication Manager server is not running, click Yes when
RRM displays a request for starting the server.
4. If the Search Device window did not appear automatically, select menu option Device >
Search.
5. In the Search Device window, select communication protocol F
OUNDATION fieldbus (if
not already selected) and click the Start Scan button (click the Advanced button if you
want to specify start and stop dress).
Now RRM searches for the transmitter. After a while, RRM shows the transmitters found
on the bus:

Table of Contents

Other manuals for Emerson Rosemount 5400 Series

Related product manuals