Section 3: Mechanical Installation
November 2014
Mechanical Installation
3.3.2 Special considerations in solids applications
The transmitter should be mounted as close to the center of the tank as possible, but
not in the center of the tank. A general practice is to mount the transmitter at
2
/
3
tank
radius from the tank wall, see Figure 3-4.
Figure 3-4. Transmitter Location in Solids Applications
The radar signal must never be shaded by the inlet nor the injected product, see
Figure 3-5.
Figure 3-5. Install the Transmitter with a Clear and Unobstructed View