282
Reference Manual
00809-0100-4026, Rev HA
Appendix H: Resource block
November 2014
Resource Block
H.2.3 Recommended actions for PlantWeb alerts
RECOMMENDED_ACTION
The RECOMMENDED_ACTION parameter displays a text string that will give a recommended
course of action to take based on which type and which specific event of the PlantWeb alerts are
active.
Table H-1. Recommended Actions
Alarm type
Failed/maint/advise/
active event
Description Recommended action
Advisory
PlantWeb alerts
simulation active
Alerts are currently being simulated.
Real alerts active in the device are
blocked (except for this alert).
Use the switch on the fieldbus
electronics board to turn simulation on
or off.
Maintenance
Device simulation
active
The measurement output from the
device is currently being simulated.
Simulation disables normal
measurement except for Internal
Temperature. Variables are GOOD if the
simulated level is GOOD and the device is
in service.
Use "Start/Stop Device Simulation" to
enable or disable simulation.
Volume measurement
warning
The level measurement is outside the
configured volume range.
Check volume configuration.
Configuration warning
The configuration of at least one
parameter is outside specifications. Refer
to the device manual for details.
Disregard this alert if the device is
working properly.
Check device configuration.
Internal temperature
out of limits
Internal temperature is outside its limits
(-40 °F/-40 °C to 176 °F/+80 °C).
Check ambient temperature at
installation site.
Volume measurement
failure
Reasons may be multiple:
Incorrect volume configuration
Level measurement invalid
Volume status is set to BAD.
2. If Level Measurement Failure is
active, clear that alert first.
3. Check volume configuration.
4. Load default database to the device
and reconfigure it.
5. If the error persists, it might indicate
a hardware error. Replace the
transmitter head.
Level measurement
failure
No valid level reading. Reasons may be
multiple:
No valid surface echo peak in the
measuring range.
Incorrect transmitter configuration
Level status is set to BAD.
1. Analyze echo curve for reason and
check device configuration.
2. Check device physical installation
(for instance, antenna
contamination).
3. Load default database to the device
and reconfigure it.
4. If the error persists, it might indicate
a hardware error. Replace the
transmitter head.
Configuration error
At least one of the configuration
parameters is outside its allowed
minimum-maximum range.
The default value for applicable
parameters is being used.
Load default database to the device
and reconfigure it.