164
Reference Manual
00809-0100-4026, Rev HA
Section 7: Service and Troubleshooting
November 2014
Service and Troubleshooting
7.15.1 Resource block
This section describes error conditions found in the Resource block. Read Ta ble 7 -9 through
Tabl e 7 -1 1 to determine the appropriate corrective action.
Block errors
Tabl e 7 -9 lists conditions reported in the BLOCK_ERR parameter.
Table 7-9. Resource Block BLOCK_ERR Messages
Table 7-10. Resource Block SUMMARY_STATUS Messages
Configuration Reg Password Enabled
Information, Ready Write Data
DB Error/ Microwave Unit Error/
Configuration Error/ Other Error
Restart transmitter
Download Application Software
Set database to default; load default
Database
•Call Service Center
SW Error/ Display Error/ Analog Out Error
Restart transmitter
•Call Service Center
(1) A malfunctioning display panel may only be replaced by service personnel at the Emerson Process Management Service Department. A display must not be replaced
when the transmitter is in operation.
Condition name and description
Other
Simulate active: This indicates that the simulation switch is in place.
This is not an indication that the I/O blocks are using simulated data.
Device fault state set
Device needs maintenance soon
Memory failure: A memory failure has occurred in the FLASH, RAM, or EEPROM
memory
Lost static data: Static data that is stored in non-volatile memory has been lost
Lost NV data: Non-volatile data that is stored in non-volatile memory has been lost
Device needs maintenance now
Out of service: The actual mode is out of service
Condition name
Uninitialized
No repair needed
Repairable
Call Service Center
Symptom Possible cause Action