Section 7: Service and Troubleshooting
November 2014
Service and Troubleshooting
7.14.7 Analog Output status
Analog Output status messages that may appear on the integral display, on the Field
Communicator or in the RRM program are shown in Ta ble 7 -7.
Table 7-7. Analog Output Status
Message Description Action
Not connected
Analog output hardware is not
connected.
Contact Emerson Process
Management Service Department.
Alarm mode
The analog output is in Alarm
Mode.
Check “Error Messages” on
page 154 and “Warning Messages”
on page 155 to find the reason for
the Alarm.
Saturated
The analog output signal value is
saturated, that is equal to the
saturation value.
No action needed.
Multidrop
The transmitter is in Multidrop
Mode. The analog output is fixed at
4 mA.
This is the normal setting when a
device is used in Multidrop
configuration.
Fixed current mode
The analog output is in fixed
current mode.
This mode is used when calibrating
the Analog Output channel.
Invalid limits
The given Upper and Lower Range
Values are invalid.
Check that the difference between
the Upper and Lower Range Value
is greater than the Minimum Span.