EasyManua.ls Logo

Emerson Rosemount 5400 Series - Rrm

Emerson Rosemount 5400 Series
314 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
253
Reference Manual
00809-0100-4026, Rev HA
Appendix D: Performing proof test
November 2014
Performing Proof Test
D.3 RRM
Prior to this test, inspect the echo curve to ensure that no disturbing echoes affecting the
measurement performance are present.
RRM: Tools / Echo Curve
1. Bypass the safety PLC or take other appropriate actions to avoid false trip.
2. Disable write protection if the function is enabled.
RRM: Select Tools, Lock / Unlock Configuration Area from the menu.
Type the password being used for this device and click OK.
3. Set Alarm mode to High Current. Using loop test, enter the mA value representing the
high alarm current. Verify that the analog output current is correct using the reference
meter.
This step tests for compliance voltage problems, such as low power supply voltage or
increased wiring resistance.
RRM: Select Setup, Output from the menu.
Make sure Alarm Mode AOut 1 is set to High Current. Click Store to save changes. Click
Loop test... and enter the Current AOut 1 value representing the high alarm current.
Click Start and verify that the output current is correct.
Click Stop to end loop test.
4. Set Alarm mode to Low Current. Using loop test, enter the mA value representing the
low alarm current. Verify that the analog output current is correct using the reference
meter.
This step tests for possible quiescent current related failures.
RRM: Set Alarm Mode AOut 1 to Low Current. Click Store to save changes. Click Loop
test... and enter the Current AOut 1 value representing the low alarm current.
Click Start and verify that the output current is correct.
Click Stop to end loop test.
Alarm Mode AOut 1
Loop test...

Table of Contents

Other manuals for Emerson Rosemount 5400 Series

Related product manuals