37
Reference Manual
00809-0100-4026, Rev HA
Section 3: Mechanical Installation
November 2014
Mechanical Installation
3.4.2 Process seal antenna
(1)
Figure 3-19. Mounting the Rosemount 5400 with Process Seal and Flange
1. Place the antenna on top of the nozzle.
2. Mount the flange and tighten the bolts cross-wise. For torque information,
see Tab le 3-9 .
3. Mount the transmitter head and tighten the nut to 40 Nm (30 Lbft).
4. Re-tighten the flange bolts after 24 hours.
(1) The mounting information applies to the updated Process Seal antenna design, released in February 2012. Antennas manufactured before
this date have wetted O-rings and require a different installation procedure. For detailed information on the updated Process Seal antenna,
see the Rosemount 5400 Series Reference Manual - Supplementary Information for Process Seal Antennas Manual Supplement (Document
No. 00809-0700-4026).
E
F
A
B
D
G
H
I
C
A. Transmitter housing
B. Nut, 40 Nm (30 Lbft)
C. Nut
D. Locking screw (ATEX)
E. Bolt
F. Flange
G. Process Seal antenna
H. Tank flange
I. Nozzle