Appendix C: Advanced configuration
November 2014
Advanced Configuration
C.4.2 Full tank handling
With the Full Tank Handling function product levels close to the antenna can be reported as a
Full Tank. Normally, measurements are not allowed closer to the antenna than specified by the
Hold Off Distance parameter. If the product level enters the Hold Off Distance region, the
transmitter reports Measurement Error and starts searching for the surface.
By setting the Level above Hold Off Distance possible parameter, the transmitter reports Full Tank
when the product level enters the Hold Off Distance region. Note that:
The region where the tank is considered full is specified by the Full Tank Detection Area
The level alarm for Full Tank is normally disabled
Amplitude
Distance
If the product surface is
lost in this region, the
transmitter presents full
tank.
Full tank
detection
area
Hold off
distance