102
Reference Manual
00809-0100-4026, Rev HA
Section 5: Basic Configuration/Start-up
November 2014
Basic Configuration/Start-up
To make a basic setup of the transmitter, do the following:
1. Check that the desired Measurement Units are selected. HART command: [2, 1, 1, 5].
2. Enter configuration parameters for the following:
Device info. HART command: [2, 2, 1]
Geometry. HART command: [2, 1, 2]
Environment. HART command: [2, 1, 3]
Volume. HART command: [2, 1, 4]
Analog Out. HART command: [2, 1, 5]
3. Run Measure and Learn. HART command: [2, 1, 6, 2]. This function creates an ATC.
4. Restart the transmitter. HART command: [2, 1, 6, 4].
To view the Echo Curve and adjust threshold settings, see “Using the Echo Curve Analyzer” on
page 137.