141
Reference Manual
00809-0100-4026, Rev HA
Section 7: Service and Troubleshooting
November 2014
Service and Troubleshooting
Register false echoes
To register false echoes:
1. Select HART command [2, 5, 1].
2. Select option 1 Found Echo Peaks to display found echoes.
3. Select option 2 Add False Echo... to register false echoes based on distance.
Threshold settings
To adjust the amplitude thresholds:
1. Select HART command [2, 5, 2].
The different echo curve options appear on the display:
2. Select option 1 Measure and Learn to create an ATC, see “ATC on page 84 for more
information.
Select option 2 Set Threshold to specify a constant Surface Threshold.
3. Click the SAVE button to store the new settings in the transmitter database.
1 Found Echo Peaks
2 Measurement Output
3 Registered False Echoes
4 Add False Echo...
5 Remove False Echo...
Peaks