180
Reference Manual
00809-0100-4026, Rev HA
Appendix A: Reference data
November 2014
Reference Data
Saturation levels
Standard: Low=3.9 mA, High=20.8 mA
Namur NE43: Low = 3.8 mA, High = 20.5 mA
Figure A-5. Alarm Levels
Load limitations
Maximum load resistance (R) is determined by the voltage level of the external power supply
(U
E
), as described by Figure A-6 to Figure A-8:
Figure A-6. Non-Hazardous Installations
Figure A-7. Intrinsically Safe Installations
Rosemount alarm level
Normal operation
3.75 mA
(1)
(1) Transmitter Failure, hardware or software alarm in Low position.
4 mA 20 mA 21.75 mA
(2)
(2) Transmitter Failure, hardware or software alarm in High position.
3.9 mA 20.8 mA
low saturation high saturation
External Power Supply Voltage U
E
(V)
Maximum Load Resistance R(
:)
Operating
region
10 20
16
30
200
400
600
800
1000
1200
1400
40 50
24
586
847
External Power Supply Voltage U
E
(V)
Maximum Load Resistance R(
:)
Operating
region