INSTALLATION DRAWING
for hazardous location installation
of CSA approved apparatus
6
1 / 1
ISSUED BY
APPROVED BY
WEEK
WEEK
PRODUCT CODE
DOC. TYPE FILE
TITLE
DWG NO. ISSUE SHEET
SCALE
1:1
1 ST ANGLE
FINISH, UNLESS
OTHERWISE STATED:
ALL DIMENSIONS ARE IN MILLIMETRES.
T h e c op y right/ownership of this document is and will remain ours.
T h e d oc ument must not be used without our authorization or brought
to th e k n ow l edge of a third party. Contravention will be prosecuted.
Rosemount Tank Radar AB, Sweden
ASSOCIATED APPARATUS
BARRIER
POWER
SUPPLY
HAZARDOUS LOCATION
NON-HAZARDOUS LOCATION
ROSEMOUNT 5400 SERIES
Intrinsically Safe Ex ia
Class I, Division 1, Groups A,B,C and D, Temperature Code T4 :
Model Entity Parameters Ambient Temperature
Limits
4-20 mA/HART IS Model Vmax <= 30V, Imax <= 130 mA
Pi <= 1W, Ci = 7.3 nF , Li = 0 uH
-50 <= Ta <= 70 deg C
Fieldbus IS Model Vmax <= 30V, Imax <= 300 mA
Pi <= 1.3W, Ci = 0, Li = 0 uH
-50 <= Ta <= 60 deg C
Fieldbus FISCO IS Model Vmax <= 17.5V, Imax <= 380 mA
Pi <= 5.32W, Ci = 0, Li = 0 uH
-50 <= Ta <= 60 deg C
2
SME-5134 0526
3
SME-5514
0644
SME-5880
0751
4
EX-CERTIFIED PRODUCT.
No modifications permitted
without reference to the
Ex-certifying Authorities.
5
SME-6019
0840
6
SME-7063
1123
ENTITY CONCEPT APPROVAL
The Entity concept allows interconnection of intrinsically safe apparatus to associated apparatus not
specifically examined in combination as a system. The approved values of maximum open circuit voltage (Voc)
and maximum short circuit current (Isc) and maximum output power (or Voc x Isc / 4), for the associated apparatus
must be less than or equal to the maximum safe input voltage (Ui), maximum safe input current (Ii), and maximum
safe input power (Pi) of the intrinsically safe apparatus. In addition, the approved maximum allowable connected
capacitance (Ca) of the associated apparatus must be greater than the sum of the interconnecting cable capacitance
and the unprotected internal capacitance (Ci) of the intrinsically safe apparatus, and the approved maximum allowable
connected inductance (La) of the associated apparatus must be greater than the sum of the interconnecting cable
inductance and the unprotected internal inductance (Li) of the intrinsically safe apparatus.
Notes :
1. Entity parameters listed (for HART/Fieldbus Model) apply only to associated apparatus with linear output.
2. Control equipment connected to the barrier must not use or generate more than 250 Vrms or Vdc.
3. Connect supply wires to the appropriate terminals as indicated on the terminal block and in the
installation documents.
4. Installations should be in accordance with ANSI/ISA-RP12.6 "Installations of Intrinsically Safe Systems
for Hazardous Locations" and the Canadian Electric Code.
5. Product options bearing the DUAL SEAL marking on the label meets the Dual Seal requirements of ANSI/ISA
12.27.01. No additional process sealing is required. For the in-service limits applicable to a specific model, see
Process Pressure/Temperature range in Appendix A of the Reference manual.