234
Reference Manual
00809-0100-4026, Rev HA
Appendix B: Product certifications
November 2014
Product Certifications
Figure B-4. Installation drawing Ex n Rosemount 5400 Series
ORIGINAL SIZE A3
2011-06-28 14:34
9240031-958_I02_P01_A3.DOCX
INSTALLATION DRAWING Exn
ROSEMOUNT 5400 SERIES
The copyright/ownership of this document is
and will remain ours. The document must not
be used without our authorization or brought
to the knowledge of a
Contravention will be prosecuted.
Rosemount Tank Radar AB, Sweden
NON-HAZARDOUS LOCATION HAZARDOUS LOCATION
HART:
42.4 VDC , 23 mA
FOUNDATION FIELDBUS:
32 VDC, 21 mA
Note 1
nA
Ui: 42.4 V
Ii: 23 mA
Pi: 1 W
Li: Negligible
Uo: 42.4 V Ci: 7.25 nF
nL Io: 23 mA Note 1
Po: 1 W
Lo > 0
Co > 7.25 nF
Notes:
1 Connect supply wires to the appropriate terminals as indicated on the terminal block label
and in the installation documents.
Input parameters for Non-sparking
Ambient
Temperature Limits
Input parameters for Energy Limited
Ambient
Temperature Limits
U
i
= 42.4 V, I
i
= 23 mA, P
i
C
i
= 7.25 nF, L
i
: Negligible
U
i
= 32 V, I
i
= 21 mA, P
i
= 0.7 W
C
i
= 4.95 nF, L
i
: Negligible
modifications permitted without
reference to the Ex