Reference Manual
00809-0100-4026, Rev HA
Appendix H: Resource block
November 2014
Resource Block
FAILED_PRI
Designates the alerting priority of the FAILED_ALM, see Alarm priority” on page 281. The
default is 0 and the recommended values are between 8 and 15.
FAILED_ACTIVE
This parameter displays which of the alarms is active. Only the alarm with the highest priority
will be displayed. This priority is not the same as the FAILED_PRI parameter described above.
This priority is hard coded within the device and is not user configurable.
FAILED_ALM
Alarm indicating a failure within a device which makes the device non-operational.
MAINT_ALARMS
A maintenance alarm indicates the device or some part of the device needs maintenance soon.
If the condition is ignored, the device will eventually fail. There are five parameters associated
with MAINT_ALARMS, they are described below.
MAINT_ENABLED
The MAINT_ENABLED parameter contains a list of conditions indicating the device or some part
of the device needs maintenance soon.
Below is a list of the conditions:
Configuration Error
Level Measurement Failure
Volume Measurement Failure
Internal Temperature Out of Limits
Configuration Warning
Volume Measurement Warning
Device Simulation Active
MAINT_MASK
The MAINT_MASK parameter will mask any of the failed conditions listed in MAINT_ENABLED. A
bit on means that the condition is masked out from alarming and will not be reported.
MAINT_PRI
MAINT_PRI designates the alarming priority of the MAINT_ALM, see “Recommended actions for
PlantWeb alerts” on page 282. The default is 0 and the recommended values is 3 to 7.
MAINT_ACTIVE
The MAINT_ACTIVE parameter displays which of the alarms is active. Only the condition with
the highest priority will be displayed. This priority is not the same as the MAINT_PRI parameter
described above. This priority is hard coded within the device and is not user configurable.