Appendix I: Analog-Input block
November 2014
Analog-Input Block
LO_PRI 29 None The priority of the LO alarm.
LO_LIM 30 EU of PV_SCALE The setting for the alarm limit used to detect the LO alarm condition.
LO_LO_PRI 31 None The priority of the LO LO alarm.
LO_LO_LIM 32 EU of PV_SCALE The setting for the alarm limit used to detect the LO LO alarm condition.
HI_HI_ALM 33 None
The HI HI alarm data, which includes a value of the alarm, a timestamp
of occurrence and the state of the alarm.
HI_ALM 34 None
The HI alarm data, which includes a value of the alarm, a timestamp of
occurrence and the state of the alarm.
LO_ALM 35 None
The LO alarm data, which includes a value of the alarm, a timestamp of
occurrence and the state of the alarm.
LO_LO_ALM 36 None
The LO LO alarm data, which includes a value of the alarm, a timestamp
of occurrence and the state of the alarm.
OUT_D 37 None Discrete output to indicate a selected alarm condition.
ALM_SEL 38 None
Used to select the process alarm conditions that will cause the OUT_D
parameter to be set.
VAR_INDEX 39 % of OUT Range
The average absolute error between the PV and its previous mean value
over that evaluation time defined by VAR_SCAN.
VAR_SCAN 40 Seconds The time over which the VAR_INDEX is evaluated.