Cerabar S/Deltabar S Description of parameters (ToF Tool)
Endress+Hauser 135
FACT. U. U. TOTAL. 1
Entry
Enter conversion factor for a customer-specific unit for totalizer 1.
The conversion factor must be entered in relation to an appropriate SI unit, e.g. m
3
for the
"Volume p. cond." FLOW-MEAS. TYPE. See also TOT. 1 USER UNIT.
Prerequisite:
TOTALIZER 1 UNIT = user unit
Example: You want the measured value to be displayed in "buckets".
MEASURED VALUE =1 m3 i 100 buckets
Entry TOT. 1 USER UNIT: bucket
Entry FACT. U. U. TOTAL. 1: 100
Result: MEASURED VALUE = 100 buckets
Factory setting:
1.0
NEG. FLOW TOT. 1
Selection
Specify way of counting negative flows for totalizer 1.
P01-xMD7xxxx-16-xx-xx-xx-003
Factory setting:
Positive
RESET TOTALIZER1
Selection
You reset totalizer 1 to zero with this parameter.
Options:
Abort (do not reset)
•Reset
Factory setting:
Abort
TOTALIZER 2 UNIT
Selection
Select unit for totalizer 2.
See also TOTAL 1. ENG. UNIT.
Factory setting:
m
3
TOT. 2 USER UNIT
Entry
Enter text (unit) for customer-specific unit for totalizer 2.
See also TOT. 1 USER UNIT.
Prerequisite:
TOTALIZER 2 UNIT = user unit
Factory setting:
_ _ _ _ _ _ _ _
FACT. U. U. TOTAL. 2
Selection
Enter conversion factor for a customer-specific unit for totalizer 2.
See also FACT. U. U. TOTAL. 1.
Prerequisite:
TOTALIZER 2 UNIT = user unit
Factory setting:
1.0
NEG. FLOW TOT. 2
Selection
Specify way of counting negative flows for totalizer 2.
See NEG. FLOW TOT. 1.
Factory setting:
Positive
ToF Tool, Table 15: OPERATING MENU SETTINGS TOTALIZER SETUP
Parameter name Description
Options
Stop on neg. flow
Dec. on neg. flow
Inc. on. neg. flow
negative flow
Total remains constant
Total decreases
Total increases
Total increases
Total increases
Total increases
positive flow