Description of parameters (ToF Tool) Cerabar S/Deltabar S
150 Endress+Hauser
ALARM DISPL. TIME
Entry
Enter alarm display time. Once the cause of the error is rectified, the alarm display time
starts running.
!
Note!
The following applies if the setting for ACK. ALARM MODE = on:
If an alarm appears and the alarm display time elapses before the alarm has been
acknowledged, the message will be cleared once it has been acknowledged.
See also these Operating Instructions, Section 11.3 "Confirming messages".
Input range:
0...999.9 s
Factory setting:
0.0 s
ToF Tool, Table 28: OPERATING MENU DIAGNOSTICS USER LIMITS
Parameter name Description
Pmin ALARM WINDOW
Entry
Customer-specific process monitoring – enter lower pressure limit.
You can use the SELECT ALARMTYPE parameter to enter how the device responds if the
operating pressure undershoots the specified value.
See also these Operating Instructions, Section 11.1 "Messages", table, Code E730 and
Section 11.2. "Response of outputs to errors".
Factory setting:
Low sensor limit •1.1
(For the low sensor limit, see PRESS. SENS LOLIM.)
Pmax ALARM WINDOW
Entry
Customer-specific process monitoring – enter upper pressure limit.
You can use the SELECT ALARMTYPE parameter to enter how the device responds if the
operating pressure undershoots the specified value.
See also these Operating Instructions, Section 11.1 "Messages", table, Code E731 and
Section 11.2. "Response of outputs to errors".
Factory setting:
High sensor limit •1.1
(For the high sensor limit, see PRESS. SENS HILIM.)
Tmin ALARM WINDOW
Entry
Customer-specific process monitoring – enter lower temperature limit.
You can use the SELECT ALARMTYPE parameter to enter how the device responds if the
operating pressure undershoots the specified value.
See also these Operating Instructions, Section 11.1 "Messages", table, Code E732 and
Section 11.2. "Response of outputs to errors".
Factory setting:
Lower sensor temperature application limit – 10 K
(For the lower temperature application limit, see Tmin SENSOR)
Tmax ALARM WINDOW
Entry
Customer-specific process monitoring – enter upper temperature limit.
You can use the SELECT ALARMTYPE parameter to enter how the device responds if the
operating pressure undershoots the specified value.
See also these Operating Instructions, Section 11.1 "Messages", table, Code E733 and
Section 11.2. "Response of outputs to errors".
Factory setting:
Upper sensor temperature application limit +10 K
(For the upper temperature application limit, see Tmax SENSOR)
ToF Tool, Table 27: OPERATING MENU DIAGNOSTICS MESSAGES
Parameter name Description