Description of device parameters (operating menu) Levelflex FMP51, FMP52, FMP54
128 Endress+Hauser
The "Level" submenu
This submenu is only visible for "Operating mode" = "Level".
Medium type
Navigation
Setup ® Advanced Setup ® Level ® Medium type
Description
Defines the type of medium
Options
• Liquid
•
Solid
Factory setting
Liquid
Medium property
Navigation
Setup ® Advanced Setup ® Level ® Medium property
Description
Defines the dielectric constant
Options
• Unknown
•
DC 1.4 ... 1.6
• DC 1.6 ... 1.9
• DC 1.9 ... 2.5
• DC 2.5 ... 4
• DC 4 ... 7
• DC 7 ... 15
• DC > 15
Factory setting
Unknown
Additonal information
Dielectric constants of important media commonly used in the industry are summarized in
the document SD106F, which can be downloaded from the Endress+Hauser web page
(www.endress.com).
Process property
Navigation
Setup ® Advanced Setup ® Level ® Process property
Description
Defines a typical rate of level change