Levelflex FMP51, FMP52, FMP54 Description of device parameters (operating menu)
Endress+Hauser 129
Options For "Medium type" = "Liquid"
•
Fast > 1 m(40")/min
• Standard < 1 m(40")/min
• Medium < 10 cm(4")/min
• Slow < 1 cm(0.4")/min
• No filter
For "Medium type" = "Solid"
• Fast > 10 m(33ft)/h
• Standard < 10 m(33ft)/h
• Medium < 1 m(3ft)/h
• Slow < 0.1 m(0.3ft)/h
• No filter
Factory setting
Standard < 1m(40")/min
Additional information
The device adjusts the signal evaluation filters and the damping of the output signal to
the typical rate of level change defined in this parameter:
For "Medium type" = "Liquid"
Process property Step response time [s]
Fast > 1m(40")/min 3
Standard < 1 m(40")/min 13
Medium < 10 cm(4")/min 38
Slow < 1 cm(0.4")/min 73
No filter < 0.8
For "Medium type" = "Solid"
Process property Step response time [s]
Fast > 10 m(33ft)/h 37
Standard < 10 m(33 ft)/h 74
Medium < 1 m(3ft)/h 145
Slow < 0.1 m (0.03ft)/h 290
No filter < 0.8
Other than the given values (e.g. intermediate values) can be defined in the
"Expert" menu. For details please refer to GP01001F, "Levelflex
FMP50/51/52/53/54/55/56/57 - Description of Device Parameters -
PROFIBUS PA".
Advanced conditions
Navigation
Setup ® Advanced setup ® Level ® Adv. conditions
Description
Defines additional process conditions (if necessary)
Options
• Build up
•
None
Additionally for "Medium type" = "Liquid"
• Emulsion layer
• Probe near bottom
Factory setting
None