Description of device parameters (operating menu) Levelflex FMP51, FMP52, FMP54
130 Endress+Hauser
Additional information
"Advanced conditions" should only be applied in the "Level" operating mode.
For two-phase media the "Emulsion layer" option ensures that always the total level is detected
(Example: Oil/condensate application).
The "Probe near bottom" option helps to improve the empty detection, especially if the probe is
mounted close to the tank bottom.
Level unit
Navigation
Setup ® Advanced setup ® Level ® Level unit
Description
Defines the level unit
Options
%
m
mm
ft
in
Factory setting
%
Additional information
The level unit may differ from the distance unit as defined in the Distance unit parameter
(® ä 116):
The distance unit is used for the basic calibration ("Empty calibration" and "Full calibration").
The level unit is used to display the (unlinearized) level.
Blocking distance
Navigation
Setup ® Advanced setup ® Level ® Blocking dist.
Setup ® Advanced setup ® Safety settings ® Blocking dist.
Description
Defines the upper blocking distance UB
Input range
0 to 200 mm (0 to 7.8 in)
Factory setting
For level measurement:
with coax probes: 0 mm
with rod and rope probes up to 8 m (26 ft): 200 mm (8")
with rod and rope probes exceeding 8 m (26 ft): 0,025 * (length of probe)