Levelflex FMP51, FMP52, FMP54 Description of device parameters (operating menu)
Endress+Hauser 131
Additional information
No echos are evaluated within the blocking
distance UB. Therefore, UB can be used to
suppress interference echos within the upper end
of the probe.
UB
A0013219
Level correction
Navigation
Setup ® Advanced setup ® Level ® Level correction
Description
Defines a level correction
Input range Depending on the selected level unit:
-100,0 to 100,0 %
-200,0 to +200,0 m
-656,2 to +656,2 ft
-7874,0 to +7874,0 inch
-200.000,0 to +200.000,0 mm
Factory setting
0%
Additional information
The value specified in this parameter is added to the measured level (before linearization).