Description of device parameters (operating menu) Levelflex FMP51, FMP52, FMP54
134 Endress+Hauser
Additional information
Echoes from within the blocking distance are not
taken into account in the signal evaluation. The
upper blocking distance is used
to suppress interference echoes at the top end of
the probe (1).
to suppress the echo of the total level in the case
of flooded bypasses (2).
1
2
UB
UB
A0013220
Level correction
Navigation
Setup ® Advanced setup ® Interface ® Level correction
Description
Defines the level correction
Input range Depending on the selected level unit:
-100,0 ... 100,0 %
-200,0 ... +200,0 m
-656,2 ... +656,2 ft
-7874,0 ... +7874,0 inch
-200.000,0 ... +200.000,0 mm
Factory setting
0%
Additional information
The value specified in this parameter is added to the measured total and interface level.