Levelflex FMP51, FMP52, FMP54 Description of device parameters (operating menu)
Endress+Hauser 143
Description
Defines the slope of the ramp in the case of a lost
echo.
t
min
0%
100%
A
B
C
A0013269
A Delay echo lost
B Ramp echo lost (positive value)
C Ramp echo lost (negative value)
Input range
-9999999,0 to + 9999999,0 %/min
Factory setting
0 %/min
Additional information
The unit for the slope of the ramp is "percentage of the measuring range per minute" (%/min).
For a negative slope of the ramp: The measured value is continuously decreased until it reaches
0%.
For a positive slope of the ramp: The measured value is continuosly increased until it reaches
100%.