Levelflex FMP51, FMP52, FMP54 Description of device parameters (operating menu)
Endress+Hauser 151
Invert output signal
Navigation
Setup ® Advanced setup ® Switch output ® Invert output signal
Description
Allows to invert the behavior of the switch output.
Options
• No
The behavior of the switch output is as described above.
•
Yes
The states Opend and Closed are inverted as compared to the description above.
"Analog input 1" ... "Analog input 6" submenus
The Analog input 1 to Analog input 6 submenus are used to configure the AO blocks of the
device.
Channel
Navigation
Setup ® Advanced setup ® Analog input 1...6 ® Channel
Diagnostics ® Measured value ® Analog input 1...6 ® Channel
Description
Allocates a measured value to the AI block.
Options
• Level linearized
•
Distance
• Interface linearized (only for Operating mode = Interface)
• Interface distance (only for Operating mode = Interface)
• Upper interface thickness (only for Operating mode = Interface)
• Terminal voltage
• Electronic temperature
• Absolute echo amplitude
• Relative echo amplitude
• Absolute interface amplitude (only for Operating mode = Interface)
• Relative interface amplitude (only for Operating mode = Interface)
• Absolute EOP amplitude
• Noise of signal
• EOP shift
Factory setting
Level linearized
PV filter time
Navigation
Setup ® Advanced setup ® Analog input 1...6 ® PV filter time
Description
Enter damping constant for AI block.
Range of values
0 to 3.4 10
38
s