EasyManua.ls Logo

Endress+Hauser Levelflex FMP53 - Digital input 1... Digital input 4 submenus; Channel; Fail safe type

Endress+Hauser Levelflex FMP53
194 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description of device parameters (operating menu) Levelflex FMP51, FMP52, FMP54
154 Endress+Hauser
"Digital input 1" ... "Digital input 4" submenus
The Digital input 1 to Digital input 4 submenus are used to configure the DI blocks of the
device.
Channel
Navigation
Setup ® Advanced setup ® Digital input 1...4 ® Channel
Diagnostics ® Measured value ® Digital input 1...4 ® Channel
Description
Allocates a switching variable to the DI block.
Options
None
Switch output
The DI block tracks the behavior of the switch output.
Factory setting
None
Additional information
If Switch output is selected, the digital output value tracks the state of the switch outut:
Switch output open: 0
Switch output closed: 1
This allocation can be inverted by the Invert parameter.
Invert
Navigation
Setup ® Advanced setup ® Digital input 1...4 ® Invert
Description
Allows to invert the digital output signal (i.e. to swap the states "0" and "1").
Options
Off
On
Factory setting
Off (i.e. no inversion)
Fail safe type
Navigation
Setup ® Advanced setup ® Digital input 1...4 ® Fail safe type
Description
Defines the output value of the DI block in case of an error.
Options
Fail safe value
The oputput value in case of an error is define in the Fail safe value parameter.
Failback value
The last valid output value before the error occurred is maintained.
Off
The output value tracks the current measuring value. The status is set to BAD.