Levelflex FMP51, FMP52, FMP54 Description of device parameters (operating menu)
Endress+Hauser 155
Factory setting
Off
Fail safe value
Navigation
Setup ® Advanced setup ® Digital input 1...4 ® Fail safe value
Prerequisite
Only visible for Fail safe type = Fail safe value.
Description
Defines the output value of the DI block in case of an error.
Range of values
00 ... FF(hex)
Factory setting
00(hex)
Out value
Navigation
Setup ® Advanced setup ® Digital input 1...4 ® Out value
Diagnostics ® Measured value ® Digital input 1...4 ® Out value
Description
Indicates the output value of the DI block.
Out status
Navigation
Setup ® Advanced setup ® Digital input 1...4 ® Out status
Diagnostics ® Measured value ® Digital input 1...4 ® Out status
Description
Indicates the status of the output value of the DI block.
Display options
• Good
•
Uncertain
• Bad
Out status HEX
Navigation
Setup ® Advanced setup ® Digital input 1...4 ® Out status HEX
Diagnostics ® Measured value ® Digital input 1...4 ® Out status HEX
Description
Indicates the hexadecimal code for the status of the output value of the AI block (status byte).