Mounting Levelflex FMP51, FMP52, FMP54
48 Endress+Hauser
XT 280 °C (536 °F)* HT 400 °C (842 °F)
MAX MAX
MAX
MAX
1 1
3
3
2
2
A0014657
å 11
Process connection with thread - FMP54, sensor version XT and HT
1 Tank insulation
2 Compact device
3 Sensor remote (feature 600)
* The XT version is not recommended for saturated steam above 200 °C (392 °F). Use the HT version instead.
MAX MAX
MAX
MAX
XT 280 °C (536 °F)*
HT 400 °C (842 °F)
1 1
3
3
2
2
A0014658
å 12
Process connection with flange - FMP54, sensor version XT and HT
1 Tank insulation
2 Compact device
3 Sensor remote (feature 600)
* The XT version is not recommended for saturated steam above 200 °C (392 °F). Use the HT version instead.
Replacing a displacer system in an existing displacer chamber
FMP51 and FMP54 are a perfect replacement for a conventional displacer system in an existing
displacer chamber. Endress+Hauser offers flanges that suit Fischer and Masoneilan displacer
chamber for this purpose (special product for FMP51; feature 100, options LNJ, LPJ, LQJ for
FMP54). Thanks to menu-guided local operation, commissioning the Levelflex only takes a few
minutes. Replacement is also possible when partially filled, and wet calibration is not required.
Your benefits:
No moving parts, thus zero-maintenance operation.
Not sensitive to process influences such as temperature, density, turbulence and vibrations.
The rod probes can be shortened or replaced easily. In this way, the probe can be easily
adjusted on site.