EasyManuals Logo

Endress+Hauser Micropilot FMR60B User Manual

Endress+Hauser Micropilot FMR60B
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
Basic safety instructions Micropilot FMR60B PROFINET with Ethernet-APL
10 Endress+Hauser
2.7 Device-specific IT security
The device offers specific functions to support protective measures by the operator. These
functions can be configured by the user and guarantee greater in-operation safety if used
correctly. An overview of the most important functions is provided in the following section:
Write protection via hardware write protection switch
Access code to change user role (applies to operation via display, Bluetooth or FieldCare,
DeviceCare, asset management tools (e.g., AMS, PDM and Web server)
Function/interface Factory setting Recommendation
Access code
(also applies to Web server login or FieldCare connection)
Not enabled (0000) Assign a customized access code during commissioning
Web server Enabled On an individual basis following risk assessment
Service interface (CDI) Enabled On an individual basis following risk assessment
Write protection via hardware write protection switch Not enabled On an individual basis following risk assessment
2.7.1 Protecting access via a password
Different passwords are available to protect write access to the parameters of the device.
Protect write access to the parameters of the device via the local display, Web browser or
operating tool (e.g. FieldCare, DeviceCare). Access authorization is clearly regulated
through the use of a user-specific access code.
User-specific access code
Write access to the parameters of the device via the local display, Web browser or
operating tool (e.g. FieldCare, DeviceCare) can be protected using the editable, user-
specific access code.
When delivered, the device does not have an access code and this code corresponds to
0000 (open).
General notes on the use of passwords
During commissioning, change the access code used when the device was delivered
When defining and managing the access code, comply with the general rules for the
generation of a secure password
The user is responsible for managing the access code and for using the code with due
care
 For further information, see →
A
  Resetting the device
2.7.2 Access via Web server
Thanks to the integrated Web server, the device can be operated and configured using a
Web browser and via PROFINET with Ethernet-APL. In addition to the measured values,
status information on the device is displayed and can be used to monitor device health.
Furthermore the device data can be managed and the network parameters can be
configured.
Access to the network is required for the PROFINET with Ethernet-APL connection.

Table of Contents

Other manuals for Endress+Hauser Micropilot FMR60B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Endress+Hauser Micropilot FMR60B and is the answer not in the manual?

Endress+Hauser Micropilot FMR60B Specifications

General IconGeneral
BrandEndress+Hauser
ModelMicropilot FMR60B
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals