Commissioning Micropilot FMR60B PROFINET with Ethernet-APL
48 Endress+Hauser
9.5 Configuring the device
9.5.1 Level measurement in liquids
A0016933
17 Configuration parameters for level measurement in liquids
R Reference point of measurement
A Length of antenna + 10 mm (0.4 in)
C 50 to 80 mm (1.97 to 3.15 in); medium εr < 2
D Distance
L Level
E "Empty calibration" parameter (= 0 %)
F "Full calibration" parameter (= 100 %)
In the case of media with a low dielectric constant, εr < 2 , the tank floor may be visible
through the medium at very low levels (lower than level C). Reduced accuracy must be
expected in this range. If this is not acceptable, the zero point should be positioned at a
distance C above the tank floor in these applications → Configuration parameters for
level measurement in liquids.
9.5.2 Commissioning with the Commissioning wizard
In FieldCare, DeviceCare, SmartBlue and on the display, the Commissioning wizard is
available to guide the user through the initial commissioning steps.
Complete this wizard to commission the device.
For each parameter, enter the appropriate value or select the appropriate option.
NOTE
If you exit the wizard before completing all required parameters, the changes you have
made will be saved. For this reason, the device may then be in an undefined state!
In this case, a reset to the default settings is recommended.