Micropilot FMR60B PROFINET with Ethernet-APL Diagnostics and troubleshooting
Endress+Hauser 57
Diagnostic
number
Short text Remedy instructions Status
signal
[from the
factory]
Diagnostic
behavior
[from the
factory]
586 Record map Recording of mapping
please wait
C Warning
Diagnostic of process
801 Supply voltage too low Increase supply voltage S Warning
802 Supply voltage too high Decrease supply voltage S Warning
825 Electronics temperature 1. Check ambient temperature
2. Check process temperature
S Warning
826 Sensor temperature out
of range
1. Check ambient temperature
2. Check process temperature
S Warning
941 Echo lost Check parameter 'DC value' S Warning
1)
942 In safety distance 1. Check level
2. Check safety distance
3. Reset self holding
S Warning
1)
952 Foam detected Check process conditions S Warning
1)
968 Level limited 1. Check level
2. Check limit parameters
S Warning
1) Diagnostic behavior can be changed.
11.7 Event logbook
11.7.1 Event history
A chronological overview of the event messages that have occurred is provided in the
Event logbook submenu. This submenu only exists if operating via the local display with
keys. In the case of operation via FieldCare, the event list can be displayed with the "Event
List / HistoROM" functionality of FieldCare.
Navigation:
Diagnostics → Event logbook → Event list
A maximum of 100 event messages can be displayed in chronological order.
The event history includes entries for:
• Diagnostic events
• Information events
In addition to the operating time when the event occurred, each event is also assigned a
symbol that indicates whether the event has occurred or is finished:
• Diagnostic event
• : Occurrence of the event
• : End of the event
• Information event
: Occurrence of the event
Calling up and closing the remedial measures
1. Press .
The message for the remedial measures for the selected diagnostic event opens.
2. Press + simultaneously.
The message about the remedial measures closes.