System integration Micropilot FMR60B PROFINET with Ethernet-APL
44 Endress+Hauser
8.3.4 Startup configuration
Startup configuration
(NSU)
The automation system adopts the configuration of the most important parameters of the device.
• Interfaces:
• Display operation
• Web server functionality
• Bluetooth activation
• Service (UART-CDI)
• System units:
• Level unit
• Volume unit
• Temperature unit
• Application:
• Maximum value
• Intermediate height
• Medium type
• Full calibration
• Empty calibration
• Diameter
• Diagnostic settings:
Diagnostic behavior for diverse diagnostic information
• Analog inputs:
Damping
8.4 System redundancy S2
A redundant layout with two automation systems is necessary for processes that are in
continuous operation. If one system fails the second system guarantees continued,
uninterrupted operation. The device supports S2 system redundancy and can communicate
simultaneously with both automation systems.
A0046154
15 Example of the layout of a redundant system (S2): star topology
1 Automation system 1
2 Synchronization of automation systems
3 Automation system 2
4 Ethernet-APL Field Switch
5 Device
All the devices in the network must support S2 system redundancy.