31 Usable measuring range
A Length of antenna + 10 mm (0.4 in)
B Usable measuring range
C 50 to 80 mm (1.97 to 3.15 in); medium εr < 2
H Vessel height
R Reference point of measurement, varies depending on the antenna system
For further information on the reference point, see →
Mechanical construction.
In the case of media with a low dielectric constant, εr < 2 , the tank floor may be visible
through the medium at very low levels (lower than level C). Reduced accuracy must be
expected in this range. If this is not acceptable, the zero point should be positioned at a
distance C above the tank floor in these applications → Usable measuring range.
The media groups and the possible measuring range are described as a function of the
application and media group in the following section. If the dielectric constant of the
medium is not known, to ensure a reliable measurement assume the medium belongs to
group B.