Proline Promass F 500 Modbus RS485 Commissioning
Endress+Hauser 103
Assign current output 1 to n
→  103
Current span
→  103
0/4 mA value
→  104
20 mA value
→  104
Fixed current
→  104
Failure mode
→  104
Failure current
→  104
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
interface / User
entry
Factory setting
Assign current output 1 to n Select process variable for
current output.
Off
Mass flow
Volume flow
Corrected volume
flow
Target mass flow
*
Carrier mass flow
*
Density
Reference density
Concentration
*
Temperature
Carrier pipe
temperature
*
Electronic
temperature
Oscillation
frequency 0
Oscillation
amplitude 0
*
Frequency
fluctuation 0
Oscillation
damping 0
Oscillation
damping
fluctuation 0
Signal asymmetry
Exciter current 0
Mass flow
Terminal number Shows the terminal numbers
used by the current output
module.
Not used
24-25 (I/O 2)
22-23 (I/O 3)
20-21 (I/O 4)
*
Current span Select current range for
process value output and
upper/lower level for alarm
signal.
4...20 mA NAMUR
4...20 mA US
4...20 mA
0...20 mA
Fixed current
Country-specific:
4...20 mA NAMUR
4...20 mA US
Signal mode Select the signal mode for the
current output.
Passive
Active
Passive