Commissioning Proline Promass F 500 Modbus RS485
104 Endress+Hauser
Parameter Prerequisite Description Selection / User
interface / User
entry
Factory setting
0/4 mA value One of the following options is
selected in the Current span
parameter (→  103):
4...20 mA NAMUR
4...20 mA US
4...20 mA
0...20 mA
Enter 4 mA value. Signed floating-point
number
Country-specific:
0 kg/h
0 lb/min
20 mA value One of the following options is
selected in the Current span
parameter (→  103):
4...20 mA NAMUR
4...20 mA US
4...20 mA
0...20 mA
Enter 20 mA value. Signed floating-point
number
Depends on country
and nominal
diameter
Fixed current In the Current span parameter
(→  103), the Fixed current
option is selected.
Defines the fixed output
current.
0 to 22.5 mA 22.5 mA
Failure mode One of the following options is
selected in the Assign current
output parameter (→  103):
Mass flow
Volume flow
Corrected volume flow
Target mass flow
*
Carrier mass flow
*
Density
Reference density
Concentration
*
Temperature
Carrier pipe temperature
*
Electronic temperature
Oscillation frequency 0
Oscillation amplitude 0
*
Frequency fluctuation 0
Oscillation damping 0
Oscillation damping
fluctuation 0
Signal asymmetry
Exciter current 0
One of the following options is
selected in the Current span
parameter (→  103):
4...20 mA NAMUR
4...20 mA US
4...20 mA
0...20 mA
Define output behavior in
alarm condition.
Min.
Max.
Last valid value
Actual value
Defined value
Max.
Failure current In the Failure mode
parameter, the Defined value
option is selected.
Enter current output value in
alarm condition.
0 to 22.5 mA 22.5 mA
* Visibility depends on order options or device settings