Proline Prowirl 73 Operation
Endress+Hauser 47
4-7 Not assigned
5-0 310 PT breakage
5-1 311 PT short-circuit
5-2 312 PT breakage
5-3 313 PT short-circuit
5-4 314 PT breakage, electronics
5-5 315 PT short-circuit, electronics
5-6 316 No T sensor
5-7 317 The self-monitoring function of the measuring device found an error in the
DSC sensor which can affect temperature measurement.
6-0 318 The self-monitoring function of the measuring device found an error in the
DSC sensor which can affect temperature and flow measurement.
6-1 355 Frequency output: the current flow is outside the set range.
6-2 Not assigned
6-3 381 The limit value for the minimum fluid temperature permitted is undershot.
6-4 382 The limit value for the maximum fluid temperature permitted is overshot.
6-5 397 The limit value for the minimum ambient temperature permitted is undershot.
6-6 398 The limit value for the maximum ambient temperature permitted is overshot.
6-7 412 No data are available in the measuring device for the combination of the current
values for the fluid pressure and fluid temperature.
7-0 421 The current flow velocity exceeds the specified limit value.
7-1 494 The Reynolds number is lower than 20 000.
7-2 511 The current output is not receiving valid data.
7-3 512 The frequency output is not receiving valid data.
7-4 513 The pulse output is not receiving valid data.
7-5 514 The status output is not receiving valid data.
7-6 515 The display is not receiving valid data.
7-7 516 Totalizer 1 is not receiving valid data.
8-0 517 Totalizer 2 is not receiving valid data.
8-1 621 Simulation frequency output
8-2 520 The desired value has not been found in the HART telegram.
8-3 521 2 values of the same kind have been found in the HART telegram.
8-4 522 The checksum of the HART telegram is not correct.
8-5 523 The time-out for receiving HART telegrams has been exceeded.
8-6 524 An algebraic sign different from that expected has been measured for the delta
heat.
8-7 525 Wet steam alarm
9-0 526 The temperature of the saturated steam is below 80 °C (176 °F).
9-1 Not assigned
9-2 Not assigned
9-3 Not assigned
9-4 Not assigned
9-5 Not assigned
9-6 Not assigned
9-7 Not assigned
Byte Bit Error no. Short error description ä 64