Commissioning Proline Prowirl 73
50 Endress+Hauser
6.3 Commissioning after installing a new electronics board
After startup the device checks whether a serial number is present. If this is not the case, the
following setup is started. For information on how to install a new electronics board, please refer to
ä 73.
6.3.1 "Commissioning" setup
!
Note!
• As soon as a serial number has been entered and saved this setup is no longer available. If wrong
information for a parameter is entered during the setup, it can be corrected in the appropriate
function via the function matrix.
• The required information (apart from language) is indicated on the device’s name plate and the
inner side of the display cover (ä 13). Additionally, the meter body MB index and the
calibration factor are indicated on the device’s meter body.
A0006765-en
Fig. 29: The setup starts once a new electronics board is installed if no serial number is available.
Esc
E
+
-
XXX.XXX.XX
HOME-POSITION
LANGUAGE
K-FACTOR
METER BODY TYPE MB
SERIAL NUMBER
Setup
complete
HOME